Three remote functions: telemetry, remote signaling, and remote control
Protection functions: three-phase three-section overcurrent protection function, zero sequence protection function, reclosing and blocking reclosing function
Intelligent distributed logic function: achieving local fault clearing, automatic fault isolation, automatic transfer of power supply, and automatic restoration of power supply in non faulty sections Logic manual, automatic reset and other functions
Remote/local operation: The remote/local closing and opening operations are mutually locked, and the control outlet is controlled by the soft and hard pressing plates for on/off
Power function: Dual power switching, automatic seamless switching to backup power supply in case of AC power loss, and automatic management (battery activation, alarm, protection) function for backup power supply
Communication function: multiple network and serial ports, supporting multiple communication protocols
Status indication: There are obvious local status indication signals for operation, communication, line faults, etc
Data processing function: arbitrary configuration and combination of data sent by the main station Distribution transformer load rate, three-phase imbalance, remote sensing exceeding limit, extreme value, qualification rate statistics, etc
Fault monitoring: receiving and forwarding fault indicator signals Coordinate with variable load cabinet to determine single-phase grounding fault
Telemetry | |
Rated voltage | AC220V/100V, accuracy ≤ 0.5% |
Rated current | 5A/1A, accuracy ≤ 0.5% |
Power (active, reactive, power factor) | ≤ 1% |
DC voltage | Accuracy ≤ 0.2% |
Remote signaling | |
Remote signaling power supply | DC24V/DC48V adaptive |
SOE resolution | ≤ 2ms |
Software anti shake time | 0-65535ms can be set |
Single/dual point remote signaling optional | |
Remote control | |
Output method | Empty contact output, pulse duration 1-65535ms can be set |
Contact rating | AC 250V/5A, DC 80V/2A, or DC 110/0.5A pure resistive load |
Contact life | On/off ≥ 105 times |